TERMEN - Differential pressure controller with flow limiter RCQoB

polski    russkij  

Self-acting differential pressure controllers with flow limiter - RCQoB

Differential Pressure Controllers with Flow Limiter RCQoB
Differential Pressure Controllers with Flow Limiter RCQoB
Differential Pressure Controllers with Flow Limiter RCQoBm
Differential Pressure Controllers with Flow Limiter mufowy RCQoB
Differential Pressure Controllers with Flow Limiter RCQoB
Differential Pressure Controllers with Flow Limiter RCQoB - construction

The self-acting differential pressure controllers with flow limiter are used in heating and industrial installations that are intended to adjust the differential pressure within the 0,2-1,6; 1-2,8 and 1-3,5 bar and set the flow rate in range 0,15-23 m3/h. That regulators are suitable to cold or hot water, (temperature up to 180°C for RCQoB regulators and up to 150°C for regulators RCQoBm) and non-flammable gases of temperature up to 80°C.

Key Features:

  • High quality of regulation.
  • Does not require conservation.
  • Requiring no external power source.

Construction:

The self-acting differential pressure controllers with flow limiter are controled by the medium which flows through the valve. For ensuring stable regulation at high differential pressures, the valve-plug (4) is balanced (5). The regulator consisting of two units:
- the valve: valve body (1), flow limiter(2), valve-seat (3), valve-plug (4), balanced plug (5), valve-stem (6);
- the actuator: impulse pipe (7), actuator discs and diaphragm (8), springs (9), actuator-stem (10), adjusting nut (11), actuator-body (12).

Priciple of operation:

The medium enters to the valve chamber (A). The limiter-plug (2) determines size of the gap between the valve-chamber A and B. Higher pressure is transmitted through the impulse pipe (7) to the actuator chamber (C). Value of the pressure in the chamber (B) is transmitted by holes in valve-plug (4) to the chamber (D). Changes of pressure between the chamber B and pressure in the chamber C, creates a force which moves the valve-plug (4). When downstream pressusre overcomes the set point of the spring, the valve-plug (4) closes to moment when pressure between the chamber C and D will be equal to spring set point (9). The size of the regulated flow is controlled by adjustment of the limiter (2). The value of pressure difference is adjust by nut (11). During the selection of the desired range of settings should be remembered that it is the sum of pressure drop in a fully open the installation and measuring the pressure drop on the limiter.

Installation:

Installation of RCQoB

For ensuring good work the regulator should be protect by the filter or the magnetic strainer. Install on horizontally pipelines. The direction flow of medium have to correspond with the arrow on the valve body.


Technical data:

Series RCQoB (flanged)
Diameter DN 15 20 25 32 40 50
Flow factor Kvs 3,2 5 8 12,5 20 32
Pressure PN 25 bar
Water flow m3/h
for pressure drop
0,2 Qmin 0,15 0,2 0,4 0,6 1,0 1,6
QMax. 1,3 2,0 3,2 5,0 8,0 13
0,5 Qmin 0,3 0,5 0,8 1,2 2,0 3,0
QMax. 2,3 3,5 5,6 8,8 14 23
Adjust range Dm=240 - 0,2-1,6; 1-2,8 bar
Dm=160 0,2-1,6; 1-3,5 bar -
Max. pressure
on the valve
12 bar
Max. temperature 180°C
Max. pressure in
the actuator chamber
20 bar

flangeds connectors PN25, PN ISO 7005-1

Series RCQoBm
Diameter DN 15 20 25
Flow factor Kvs 3,2 4,5 6,3
Pressure PN 16 bar
Water flow m3/h
for pressure drop
0,2 Qmin 0,15 0,2 0,3
QMax. 1,3 1,8 2,6
0,5 Qmin 0,3 0,4 0,6
QMax. 2,3 3,2 4,5
Adjust range Dm=160 0,2-1,6; 1-3,5 bar
Max. pressure
on the valve
12 bar
Max. temperature 150°C
Max. pressure in
the actuator chamber
16 bar

Dimensions [mm]:

Pressure regulator with flow limiter RCQoB flanged Pressure regulator with flow limiter RCQoB screwed
Pressure regulator with flow limiter RCQoB flanged Pressure regulator with flow limiter RCQoB screwed


DN 15 20 25 32 40 50
H1 76,5 82,5 82,5 94 102 110
H2 63 66 66 - - -
H1Max. 336 344 347 360 362 384
H2Max. 318 344 333 - - -
L1 130 150 160 180 200 230
L2 75 80 85 - - -

Value ranges:

Indicate value range 20 50 20 50
Adjust range Δ p [bar] 0,2 0,5 0,2 0,5
actuator series Dm=160 Dm=240
Selection of self-acting differential pressure regulator with flow limiter