TERMEN - Air Separators SEP

polski    russkij  

Separatory powietrza - SEP

Air separator SEP
Air separator SEP
Air separator SEP - budowa
Air separator SEP - construction

Air Separators are designed to remove air dissolved in water. Air separators are used in heating installations in the site where the water temperature is highest (for the boiler or heat exchanger). The use of air separators reduces the corrosion in the installation, pumps failure as a result of a cavitation, flow noise and loud work if the installation.

Key Features:

  • maintenance-free removal of air dissolved in water

Construction:

Air separator is constructed as a steel vessel low-carbon steel painted externally also stainless steel version available). On the coat (1) there are two connections, inlet (2) and outlet (3), are used to connect the installation. In filling the vessel are installed special rings (4) designed to separate the air contained in water. To get rid of air at the top of the tank is installed an automatic air release valve (5). For the purification precipitated from the separator air pollutants during operation in bottom of the tank is mounted connector (6), which connects the drain valve.



Technical data:

TYP DN Capacity
dm³
Temperature
°C
Pressure
bar
Weight netto
kg
Dimmensions
D L H1 H
SEP 15 15 1,1 150 6 3 108 265 105 210
SEP 20 20 1,1 3,5 108 265 105 210
SEP 25 25 1,1 3,8 108 265 105 210
SEP 32 32 1,1 4,4 108 265 105 210
SEP 40 40 4,6 11 159 295 120 305
SEP 50 50 4,6 12 159 295 120 305
SEP 65 65 4,6 13 159 295 120 305
SEP 80 80 30 27 273 450 195 600
SEP 100 100 30 30 273 450 195 600
SEP 125 125 47 52 324 500 300 780
SEP 150 150 47 55 324 500 300 780
SEP 200 500 on order - DN200 to DN500


- flanges PN16
- flanges dimmensions PN-ISO 7005-1